Version
Power supply, switch-mode power supply unit, 24 V
AC failure bridging time @ Inom
min. 20 ms
Current limiting
> 120% IN
Derating
> 60°C / 75% @ 70°C
Earth leakage current, max.
3.5 mA
Housing version
Metal, corrosion resistant
Mounting position, installation notice
Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between.
MTBF
-
- According to Standard:
- SN 29500
-
- Operating time (hours), min.:
- 1,500,000 h
-
- Ambient temperature:
- 25 °C
-
- Input voltage:
- 230 V
-
- Output power:
- 120 W
-
- Duty cycle:
- 100 %
Power factor
-
- Power factor typical:
- 0.9
-
- Input voltage:
- 230 V
-
- Ambient temperature:
- 25 °C
-
- Output power:
- 120 W
Power loss, nominal load
14.8 W
Protection against reverse voltages from the load
30…35 V DC
Short-circuit protection
Yes
Status indication
LED red/green and relay (≥21.6 V DC LED green, relay on/ ≤20.6 LED red, relay off)
Surge voltage category
III